Sincerely welcome to visit our factory at your convience. Customer could witness their order production real conditions by online videos or photos at any time during production.
STRUCTURE
Panels and base frame are made from galvanized steel
protected with polyester powder painting to ensure total
resistance to atmospheric agents.
HERMETIC COMPRESSOR
The units use high efficiency, hermetically sealed,
compressors, oil return lubrication and rubber vibration
damper. The thermal overload cut-out, phase sequence
relay and crankcase heater are integrated as the security
protection to enhance reliability and performance.
AXIAL FAN
External rotor type axial fans, equipped with three phase
direct drive motors, low noise 8 poles, protection level
IP54, provided with a protective outlet grille.
EVAPORATOR
Evaporator built with high efficiency plate type heat
exchanger, factory insulated with flexible close cell
material.
CONDENSER
Condenser built with seamless internal screw thread
copper tubes mechanically expanded into blue wave
hydrophilic aluminum fins.
HYDRAULIC CIRCUIT
Hydraulic circuit built with galvanized pipe, complete with
water discharge connection for tube in tube heat exchanger
and flange type hydraulic connectors in two directions easy
for connections from both sides of the units.
ELECTRIC PANEL
Electric panel consist of: Compressor contactor, fan motor
contactor, compressor protection breaker, fan protection
breaker, phase sequence relay and microprocessor with
function display (display only for master/packaged unit)
Automatic operation dramatically reducing maintenance
cost thanks to reliable microprocessor system.
OPTIONAL
• Pressure differential/Flow switch;
• Metallic filter for hydraulic circuit;
• Water pump;
• Rubber anti-vibration mounting..
• BMS
• Stainless steel covering
Model |
08 |
14 |
16 |
Power supply |
V/Ph/Hz |
220/1/50 |
220/1/50 |
220/1/50 |
7ºC
ambient temp |
Heating capacity |
kW |
8 |
13.5 |
16 |
Input power |
kW |
2.6 |
4.4 |
5.2 |
Input current |
A |
12.4 |
21.1 |
24.8 |
Minus 12ºC
ambient temp |
Heating capacity |
kW |
5.1 |
8.3 |
9.7 |
Input power |
kW |
2.37 |
3.9 |
4.55 |
Input current |
A |
11 |
20.8 |
24.7 |
35ºC
ambient temp |
Cooling capacity |
kW |
7 |
11.5 |
13.5 |
Input power |
kW |
2.55 |
4.2 |
5.1 |
Compressor |
/ |
Enhanced Vapor Injection (EVI) scroll |
Refrigerant |
Type |
/ |
R22/R407C |
Charge volum |
kg |
3.5 |
4.2 |
2*3.5 |
Gas pipe size |
mm |
15.88 |
19.05 |
2*15.88 |
Liquid pipe size |
mm |
9.52 |
9.52 |
2*9.52 |
Suit ambient temp range |
/ |
Minus 25ºC to 45ºC |
User side
heat exchanger |
Type |
/ |
High efficiency plate type or tank type |
Water flow |
m³/h |
1.2 |
2 |
2.4 |
Water pipe size |
mm |
DN25 |
Air direction |
/ |
side |
side |
side |
Outdoor unit |
Dimension |
mm |
1025*375*845 |
1025*375*1385 |
1160*565*1455 |
Net weight |
kg |
80 |
102 |
185 |
Noise |
dB(A) |
≤60 |
≤66 |
≤63 |
Indoor unit |
Dimension |
mm |
430*250*680 |
430*250*680 |
727*290*610 |
Net weight |
kg |
30 |
40 |
50 |
Noise |
dB(A) |
≤40 |
≤40 |
≤40 |
Factory View
Production Machinery
Test Lab
Air cooled water chiller Production Line